http://www.spinachbase.org/https://duniapermainan.id/https://borobudur.site/https://beritamakan.xyz/http://lesfergusonjr.com/https://www.drafthorsejournal.net/https://ajudanze.us/https://soykb.org/https://www.laoplazahotel.com/https://bidpropamkaltara.com/https://www.inmercociudades.org/https://hanomantoto.vip/https://togeljackpot.bio/https://wsf2024nepal.org/https://www.ha-software.com/https://www.demo.mimikakab.go.id/https://alapp.selumakab.go.id/main/https://www.aveironet.com/https://motocofservice.com/https://missglobalnigeria.com/https://gilchristfliegen.com/https://cosmictoto.id/https://alapp.selumakab.go.id/log/https://borobudurbet-com.net/https://auroratotosatu.net/https://auroratoto-2.com/https://totocosmic.net/
Model Selection

Model Selection

Model Selection

Precautions in selecting a model

* Actual cooling capacity can be affected by airtightness of an enclosure, placement of heat generators and dirt on the capacitors, evaporators or filters. It is recommended to select a larger model than minimum requirements.
* Do not set the internal temperature at unnecessarily low level.
* When the enclosure is located near a furnace or any place exposed to heat radiation, select a larger model than the calculation.

Values required for model selection

For evaluating a cooling capacity of an enclosure cooler,the following values are required.

機種選定に必要な制御盤の使用条件

 

If desired setting temperature is lower than the max. ambient temperature

最高外気温度より盤内希望設定温度が低い場合

 

If desired setting temperature is higher than the max. ambient temperature

最高外気温度より盤内希望設定温度が高い場合

 

* Heat intrusion rate U for an iron-made enclosure is generally 5 to 6〔W/(m2・K)〕. In this example,U=5〔W/(m2・K)〕is used.
* This information has been adapted from “Technical data No. 005-2005 Cooling performance evaluation test method for refrigeration cycle cabinet coolers”by Thermal Solution Equipment for Cabinet Technical Association,Japan.